Quote for 4SE00079-3 Heinemann Electric Co Inc Part with NSN 5925-01-048-0562

Part Number:  4SE00079-3
Alternate P/N:  4SE000793
Manufacturer:  heinemann electric co inc
NIIN:  10480562
Item Name :  circuit breaker
CAGE Code:  L3330
INC Code:  00136
Country:  USA
NCB Code:  01
FSG:  59 Electrical and Electronic Equipment Components
Last Updated:  01-19-2026

Are you looking quote for part 4SE00079-3? The Heinemann Electric Co Inc-manufactured component (CAGE Code: L3330) is documented under NSN 5925-01-048-0562 as Circuit Breaker. For the fastest quote, please complete our RFQ form with details about 4SE00079-3. We guarantee a response within 15 minutes.

ASAP Components provides the verified 4SE00079-3, classified under INC 00136, FSG 59 Electrical and Electronic Equipment Components, FSC 5925 Circuit Breakers, NIIN 01-048-0562, and NCB 01. Submit your requirements today to receive immediate pricing and availability information.

Please fill out below form for 4SE00079-3

“*” Required Fields Are Compulsory

NSN Information for Part Number 4SE00079-3 with NSN 5925-01-048-0562, 5925010480562

NSNFSCNIINCLSHazmatDEMILCancelled NSN
5925-01-048-0562

Item PartTypeName:

CIRCUIT BREAKER

59250104805620P
CIICHCCESDPMICCriticalityENAC
U A
Part NumberISCRNVCRNCCHCCMSDSSADC
3XAM1516MG3-15-221CA

Characteristics Data of NSN 5925-01-048-0562, 5925010480562

MRCCriteriaCharacteristic
AAQLBODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
ADAQBODY LENGTH3.709 INCHES MINIMUM AND 3.729 INCHES MAXIMUM
ADATBODY WIDTH3.042 INCHES MINIMUM AND 3.062 INCHES MAXIMUM
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH3.053 INCHES MINIMUM AND 3.073 INCHES MAXIMUM
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.021 INCHES MINIMUM AND 1.041 INCHES MAXIMUM
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.021 INCHES MINIMUM AND 1.041 INCHES MAXIMUM
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHT0.146 INCHES MINIMUM AND 0.166 INCHES MAXIMUM
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCE3.239 INCHES NOMINAL
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC ALL LOCATIONS
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS208.0 AC ALL LOCATIONS
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1500.0 AC ALL LOCATIONS
CPRHCIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
CPRJTRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
CPRLTRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE,TWO,AND THREE LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
CQJXNOMINAL THREAD SIZE0.138 INCHES
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT5.500 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
CWJKCASE MATERIALPLASTIC
FREQFREQUENCY IN HERTZ60.0 ALL LOCATIONS
THSDTHREAD SERIES DESIGNATORUNC
TTQYTERMINAL TYPE AND QUANTITY6 THREADED STUD

Schedule B & Trade

End Use : 20005 Electric apparatus
Schedule B : 8536200040 (NAICS 335313) Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi
SITC : 77252 Automatic circuit breakers for a voltage not exceeding 1, 000 volts

Identification

CRITL The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
HMIC P - Indicates there is no information in the hmirs. The nsn is in a fsc in table ii of federal standard 313 and a msds may be required by the user. The requirement for a msds is dependent on a hazard determination of the supplier or the intended end use of item.
PMIC A - Item does not contain precious metal.

NSN Management Codes

AAC Z
Classification Control U
MGMT_CTL 9b-----
Quantity per pack 1
Repariability
Shelf Life N/A
SOS Sms
Unit of Measure Ea

Freight Information

ACC: H - Instruments/equipment/supplies for radio, communications, electrical, laboratory, etc. (includes signal corps)
ADC: A - Shipment is not a consolidation and does not exceed 84 inches in any dimension.
LTL: P - 77.5
NMFC: 061300 - Circuit breaker/switch noi
SHC: 9 - Other or no special handling required (sh)
TCC: Z - No special type of cargo code applicable
WCC: 658 - Electrical appliances, small

ASAP Semiconductor’s Certifications And Memberships



bottom to top