Are you looking quote for part SM3-0-25-230-400-58? The Eaton Corporation-manufactured component (CAGE Code: 74193) is documented under NSN 5925-00-079-6662 as Circuit Breaker. For the fastest quote, please complete our RFQ form with details about SM3-0-25-230-400-58. We guarantee a response within 15 minutes.
ASAP Components provides the verified SM3-0-25-230-400-58, classified under INC 00136, FSG 59 Electrical and Electronic Equipment Components, FSC 5925 Circuit Breakers, NIIN 00-079-6662, and NCB 00. Submit your requirements today to receive immediate pricing and availability information.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-00-079-6662 Item PartTypeName: CIRCUIT BREAKER | 5925 | 000796662 | P | |||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | ||||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| SM3-0-25-230-400-58 | 1 | 9 | 3 |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ABXD | BUSHING LENGTH | 0.360 INCHES MINIMUM AND 0.380 INCHES MAXIMUM |
| ADAQ | BODY LENGTH | 1.448 INCHES MINIMUM AND 1.510 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 0.567 INCHES MINIMUM AND 0.629 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.870 INCHES MINIMUM AND 0.880 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.524 INCHES MINIMUM AND 1.586 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 1 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 250.0 MILLIAMPERES AC SINGLE LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 230.0 AC SINGLE LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
| CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 0.800 MINIMUM AND 3.000 MAXIMUM SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.400 MINIMUM AT 150 PCT AND 2.000 MAXIMUM AT 150 PCT AND 0.150 MINIMUM AT 200 PCT AND 0.600 MAXIMUM AT 200 PCT AND 0.040 MINIMUM AT 300 PCT AND 0.200 MAXIMUM AT 300 PCT SINGLE LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND EXPLOSION RESISTANT AND HERMETICALLY SEALED |
| FREQ | FREQUENCY IN HERTZ | 400.0 SINGLE LOCATION |
| THSD | THREAD SERIES DESIGNATOR | UNEF |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 WIRE HOOK |
| End Use : 20005 | Electric apparatus |
|---|---|
| Schedule B : 8536200040 (NAICS 335313) | Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi |
| SITC : 77252 | Automatic circuit breakers for a voltage not exceeding 1, 000 volts |
| CRITL | The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. |
|---|---|
| HMIC | P - Indicates there is no information in the hmirs. The nsn is in a fsc in table ii of federal standard 313 and a msds may be required by the user. The requirement for a msds is dependent on a hazard determination of the supplier or the intended end use of item. |
| PMIC | U - Precious metal content is unknown |
| ACC: | H - Instruments/equipment/supplies for radio, communications, electrical, laboratory, etc. (includes signal corps) |
|---|---|
| ADC: | A - Shipment is not a consolidation and does not exceed 84 inches in any dimension. |
| LCL: | P - 77.5 |
| LTL: | P - 77.5 |
| NMFC: | 061300 - Circuit breaker/switch noi |
| SHC: | 9 - Other or no special handling required (sh) |
| TCC: | Z - No special type of cargo code applicable |
| WCC: | 658 - Electrical appliances, small |