| MRC | Criteria | Characteristic |
|---|
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 9.313 INCHES MINIMUM AND 9.437 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 4.063 INCHES MINIMUM AND 4.187 INCHES MAXIMUM |
| ADAU | BODY HEIGHT | 3.751 INCHES MINIMUM AND 3.875 INCHES MAXIMUM |
| ADTV | CASE MATERIAL | PLASTIC |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.782 INCHES MINIMUM AND 3.906 INCHES MAXIMUM |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.313 INCHES MINIMUM AND 1.437 INCHES MAXIMUM |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.281 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 7.063 INCHES MINIMUM AND 7.187 INCHES MAXIMUM |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.313 INCHES MINIMUM AND 1.437 INCHES MAXIMUM |
| AFJN | III FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.438 INCHES MINIMUM AND 0.562 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 3 |
| APNQ | III ARC QUENCHING METHOD | DEION |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
| BBRG | III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | III SPECIAL HANDLING FEATURE | MAGNETIC |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 208.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 50.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 210.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |